Home › Answers › 2 kW induction cooker

What breaker and wire for a 2 kW induction cooker?

230 V (Philippines): a 15 A breaker on 2 mm² THHN, for runs up to 30 m, on its own circuit.
120/240 V (US): a 15 A breaker on 14 AWG copper at 240 V, for runs up to 100 ft.

Worked out like the lab's calculators: a continuous load (on for three hours or more) is sized at 125 % of its running current, and the wire is rated for the breaker.

230 V: the Philippines (PEC), mm² wire

Run (one way)BreakerWireVoltage dropFor a long run
10 m15 A2 mm² THHN1.5 V (0.7 %)fine
20 m15 A2 mm² THHN3.0 V (1.3 %)fine
30 m15 A2 mm² THHN4.6 V (2.0 %)fine

Running current 8.7 A at 230 V; × 1.25 = 10.9 A. Check it in the calculator.

120/240 V: the United States (NEC), AWG wire

Run (one way)BreakerWire (THHN, copper)Voltage dropFor a long run
30 ft15 A14 AWG1.3 V (0.5 %)fine
60 ft15 A14 AWG2.6 V (1.1 %)fine
100 ft15 A14 AWG4.3 V (1.8 %)fine

2,000 W induction cooktop at 240 V: 8.3 A running, 10.4 A at 125 %. NEC 210.19/210.20 (125 %), Table 310.16 at 75 °C, 240.4(D) for 14–10 AWG. Check it in the calculator.

Why these sizes

  1. The breaker protects the wire, not the appliance: the wire must carry at least what the breaker lets through.
  2. A load that runs for hours heats the wire and the breaker: both are sized at 125 % so they stay inside their rating.
  3. Long runs lose voltage in the copper: over 3 % the appliance runs hot and weak, so a longer run gets a bigger wire than the current alone asks for.

Open it on the benchWire the circuit in the lab, overload it and watch the breaker.

For planning and learning. Use the appliance's nameplate (amps, MCA and MOCP) when you have it, follow your local electrical code, and have a licensed electrician do work on a building's wiring.

In other 230 V countries (the UK, the EU, Australia), wire is also sold in mm² but the code and the breaker sizes differ: follow your local code.