Aircon branch circuit: 1.5 HP on 3.5 mm² and a 20 A breaker, on its own
Mains through a 20 A breaker and 3.5 mm² wire to a 1.5 HP non-inverter aircon on its own outlet. The tests share the circuit with the kitchen and swap in 2.0 mm² to see what gives. An aircon gets its own circuit: 3.5 mm² THHN (12 AWG) on a 20 A breaker for a 1 HP or 1.5 HP unit, 5.5 mm² on 30 A for 2 HP and up. The running current is modest (a 1.5 HP draws about 6 A) but every start pulls about 40 A for half a second, and a circuit shared with the kitchen is what trips. Philippine Electrical Code practice: lighting on 2.0 mm² (14 AWG) and a 15–20 A breaker (here 10 A), outlets on 3.5 mm² (12 AWG) and a 20 A breaker, big appliances on their own circuit.

Build it in the labGuided build, test sheet and fault finding, free in your browser.
Parts list
Test procedure
Each test has an expected value and a pass range, like a factory test sheet:
- Running current, 1.5 HP
- Start surge seen by the breaker
- Cable sized for the breaker
- A 2 HP aircon, and the kitchen outlet on the same 20 A: two kettles and the flat iron
- Short circuit in a damaged aircon cord
How it works
What it does: Mains through a 20 A breaker and 3.5 mm² wire to a 1.5 HP non-inverter aircon on its own outlet. The tests share the circuit with the kitchen and swap in 2.0 mm² to see what gives.
Build it (guided or ready-made), then run its test procedure below. Every test has an expected value and a pass range, just like a factory test sheet.
Background
Anong breaker at wire ang para sa aircon? 3.5 mm² and 20 A for 1 to 1.5 HP; 5.5 mm² and 30 A for 2 HP; always its own circuit from the panel.
More builds: power, transformers and three-phase
- Adjustable bench supply 1.25–20 V
- Light with one switch
- Staircase light: two 3-way switches
- Fan and light on a 2-gang switch
- Outlet circuit: three outlets on a 20 A breaker
- House panel: main breaker and four branch circuits
- RCD protection: someone touches a live wire
- Water heater circuit: 3.5 kW on 5.5 mm² and a 30 A breaker