Water heater circuit: 3.5 kW on 5.5 mm² and a 30 A breaker
Mains through a 30 A breaker and 5.5 mm² wire to a 3.5 kW storage water heater. The tests raise it to 5 kW and try the wrong wire. An instant or storage water heater is the biggest load in most Filipino homes: 3.5 kW is 16 A all the time it heats, and a 5 kW unit is 23 A. It gets its own circuit, 5.5 mm² THHN (10 AWG) on a 30 A breaker, and 8.0 mm² on 40 A for 5 kW. Put it on the 2.0 mm² lighting wire and the wire runs hot long before the breaker notices. Philippine Electrical Code practice: lighting on 2.0 mm² (14 AWG) and a 15–20 A breaker (here 10 A), outlets on 3.5 mm² (12 AWG) and a 20 A breaker, big appliances on their own circuit.

Build it in the labGuided build, test sheet and fault finding, free in your browser.
Parts list
Test procedure
Each test has an expected value and a pass range, like a factory test sheet:
- 3.5 kW heating
- Cable sized for the breaker
- A 5 kW heater on the same 30 A circuit
- 5 kW on a 15 A breaker (the old lighting breaker)
- 3.5 kW on 2.0 mm² lighting wire with the 30 A breaker
How it works
What it does: Mains through a 30 A breaker and 5.5 mm² wire to a 3.5 kW storage water heater. The tests raise it to 5 kW and try the wrong wire.
Build it (guided or ready-made), then run its test procedure below. Every test has an expected value and a pass range, just like a factory test sheet.
Background
Water heater na lagi nagti-trip? Either it shares a circuit, or the breaker is too small for the element. Hot wire with no trip is the dangerous case: a breaker protects the cable only when the cable is rated for the breaker.
More builds: power, transformers and three-phase
- Adjustable bench supply 1.25–20 V
- Light with one switch
- Staircase light: two 3-way switches
- Fan and light on a 2-gang switch
- Outlet circuit: three outlets on a 20 A breaker
- House panel: main breaker and four branch circuits
- RCD protection: someone touches a live wire
- Aircon branch circuit: 1.5 HP on 3.5 mm² and a 20 A breaker, on its own