Home › Builds › Water heater circuit: 3.5 kW on 5.5 mm² and a 30 A breaker

Water heater circuit: 3.5 kW on 5.5 mm² and a 30 A breaker

Bench build · Power, transformers and three-phase · Intermediate · about 20 minutes

Mains through a 30 A breaker and 5.5 mm² wire to a 3.5 kW storage water heater. The tests raise it to 5 kW and try the wrong wire. An instant or storage water heater is the biggest load in most Filipino homes: 3.5 kW is 16 A all the time it heats, and a 5 kW unit is 23 A. It gets its own circuit, 5.5 mm² THHN (10 AWG) on a 30 A breaker, and 8.0 mm² on 40 A for 5 kW. Put it on the 2.0 mm² lighting wire and the wire runs hot long before the breaker notices. Philippine Electrical Code practice: lighting on 2.0 mm² (14 AWG) and a 15–20 A breaker (here 10 A), outlets on 3.5 mm² (12 AWG) and a 20 A breaker, big appliances on their own circuit.

Water heater circuit: 3.5 kW on 5.5 mm² and a 30 A breaker: the finished build running on the simulator's bench

Build it in the labGuided build, test sheet and fault finding, free in your browser.

Parts list

Test procedure

Each test has an expected value and a pass range, like a factory test sheet:

  1. 3.5 kW heating
  2. Cable sized for the breaker
  3. A 5 kW heater on the same 30 A circuit
  4. 5 kW on a 15 A breaker (the old lighting breaker)
  5. 3.5 kW on 2.0 mm² lighting wire with the 30 A breaker

How it works

What it does: Mains through a 30 A breaker and 5.5 mm² wire to a 3.5 kW storage water heater. The tests raise it to 5 kW and try the wrong wire.

Build it (guided or ready-made), then run its test procedure below. Every test has an expected value and a pass range, just like a factory test sheet.

Background

Water heater na lagi nagti-trip? Either it shares a circuit, or the breaker is too small for the element. Hot wire with no trip is the dangerous case: a breaker protects the cable only when the cable is rated for the breaker.