Home › Lessons › Electrical installation › Reading electrical plans

Reading electrical plans

Electrical installation · Intermediate · about 20 minutes · part of Electrical Installation and Maintenance (NC II-aligned)

You will be able to read a set of electrical plans: find each outlet, switch and fixture, follow a circuit back to the panel, and read the schedule of loads. Plans are the contract between the designer and the installer, so reading them right saves rework.

Reading electrical plans: the circuit on the simulator's bench

Open this lesson in the labFree, in your browser, no account needed.

How it works

The sheets in a set of plans

SheetWhat it shows
Lighting layoutA floor plan with every lighting fixture and switch, and lines showing which switch controls which fixture.
Power layoutConvenience outlets, special-purpose outlets (aircon, water heater, range), and the circuit each belongs to.
Single-line diagramThe whole distribution system drawn with one line per circuit: service, meter, main breaker, panelboards, feeders and branch breakers, with wire and breaker sizes.
Riser diagramA vertical view of a multi-storey building: which panel is on which floor and the feeders that rise between them.
Schematic / wiring diagramThe actual connections of a control circuit, such as a motor starter or a timer-controlled light, with every wire drawn.
Schedule of loadsA table of every circuit in a panel: load, current, breaker, wire and conduit.
Legend and general notesWhat each symbol means on this job, and rules such as wire type, minimum sizes, mounting heights and the code to follow.

Always read the legend and notes first. Symbols vary between designers, and the notes often settle questions the layout leaves open.

Common symbols, in words

The shapes below are the ones used by most Philippine and US-style plans. The legend on your plan is what counts.

ItemUsual symbol
Ceiling lighting outletA circle, sometimes with a letter for the fixture type
Wall-mounted lightA circle with a short line joining it to the wall
Fluorescent or linear LED fixtureA long thin rectangle
Duplex convenience outletA small circle with two parallel lines through it
Weatherproof outletThe outlet symbol with "WP" beside it
Special-purpose outletA triangle or a circle with a letter (for example "AC" for aircon), as the legend says
Single-pole switchThe letter "S"
Three-way and four-way switch"S" with a small "3" or "4"
PanelboardA rectangle, half shaded or with a label such as "LP" or "PP"
Junction boxA small circle or square marked "J"
Wiring concealed in ceiling or wallA solid line
Wiring concealed in floorA dashed line
Home run to panelA line ending in an arrow, labelled with the panel and circuit number
Number of wires in a runShort slash marks across the line (often a longer one for the grounding conductor)

Circuit numbers and home runs

Each outlet or fixture on a layout carries a small number: the circuit it is on. All outlets marked "2" belong to circuit 2 in that panel. The designer draws the wiring from outlet to outlet and ends it with an arrow pointing roughly toward the panel. That arrow is the home run: the length of wire from the last box of the circuit back to the panelboard. It is drawn short only to save clutter; you route it on site along the path the notes allow. A label such as "LP-2" means panel LP, circuit 2.

Slash marks across a run tell you how many conductors are in that piece of conduit. A run with two hot wires, a switch leg and a grounding conductor needs a bigger conduit than a plain two-wire run, and the marks warn you of that.

Reading the schedule of loads

CktDescriptionVAVoltageCurrent (A)BreakerWireConduit
1Lighting outlets, ground floor6002302.6115 A, 2P2 × 2.0 mm² THHN + 2.0 mm² G15 mm PVC
2Convenience outlets, living/dining1,4402306.2620 A, 2P2 × 3.5 mm² THHN + 3.5 mm² G20 mm PVC
3Aircon, bedroom 11,8002307.83Per planPer planPer plan

This is a made-up example to show the columns. VA is the load assigned to the circuit (for outlets, designers often use a fixed figure per outlet, such as 180 VA, under the load-calculation rules of the code). Current is VA ÷ voltage: 600 ÷ 230 = 2.61 A, 1,440 ÷ 230 = 6.26 A. Breaker gives the trip rating and the number of poles (2P on a line-to-line 230 V service). Wire gives the number, size and type of conductors, including the grounding conductor ("G" or "E"). Conduit gives the trade size. The bottom of the schedule totals the load, which sizes the main breaker and feeder. The sizes in the example follow common Philippine practice; on a real job you install exactly what the schedule says.

Scales

Layouts are drawn to scale, written in the title block, for example 1:100 (1 mm on paper is 100 mm on site) or, on US-style plans, a fraction of an inch to a foot. Use a scale ruler, not a normal ruler, and check one known dimension (a room width written on the plan) before measuring others. Prints can shrink or be reduced, so written dimensions beat measured ones. Never scale a single-line diagram or a schematic: they are not drawn to scale.

Checking drawings against the site

On the job

Try it on the bench

  1. Treat the house bench as a small plan: write down which breaker feeds each lamp, outlet and appliance, like a schedule of loads.
  2. For each circuit, read the load in watts from the parts and work out the current at 230 V (I = P / V). Check your answer with the clamp meter.
  3. Open each breaker in turn and see which loads go off. Does it match your schedule?

Parts on the bench

In the course

Electrical Installation and Maintenance (NC II-aligned), module “3 · Reading electrical plans”.

More on electrical installation