Home › Lessons › Electrical installation › Testing and turnover

Testing and turnover

Electrical installation · Intermediate · about 20 minutes · part of Electrical Installation and Maintenance (NC II-aligned)

You will be able to inspect and test a finished installation in the right order, from visual checks and dead tests to live and functional tests, record the results, and hand the job over with complete documents. Testing is how you prove the work is safe before anyone else uses it.

Testing and turnover: the circuit on the simulator's bench

Open this lesson in the labFree, in your browser, no account needed.

How it works

The order of tests

Tests are done in a set order: dead tests first, with the supply off and locked out, then live tests. A fault found by a dead test (a short, a broken ground, bad insulation) is found safely; the same fault found by switching on could cause an arc or a shock.

  1. Visual inspection
  2. Continuity of grounding conductors and of circuit conductors
  3. Insulation resistance
  4. Polarity (dead check)
  5. Energize, then live checks: voltage, polarity and grounding at outlets
  6. RCD tests
  7. Functional test of every circuit

Visual inspection

Continuity tests

With the supply off, use a multimeter or low-resistance ohmmeter on its continuity range.

Insulation-resistance test

The insulation-resistance tester applies a DC test voltage between conductors, and between each conductor and ground, and reads the resistance through the insulation. For 230 V circuits the usual test voltage is 500 V DC.

  1. Supply off, locked out, proven dead.
  2. Disconnect or unplug electronics and anything that could be damaged: LED drivers, dimmers, timers, SPDs, RCDs with electronics, appliances, and lamps where practical. The test voltage can destroy them, and connected loads also give false low readings.
  3. Open lighting switches or link across them so the whole circuit is tested.
  4. Test line to line, and each line (and neutral if present) to ground.
  5. Read the value after the reading settles. Afterwards, let the tester discharge the circuit before touching it: long runs store charge.

Acceptance values come from the job specification and the code that applies. A minimum of 1 MΩ at 500 V DC is widely used for low-voltage circuits; a new installation in good condition usually reads much higher. A low reading points to damaged insulation (a nick during the pull, a screw through a wire) or moisture in a box. Split the circuit at boxes to find the section with the fault.

Polarity and grounding checks

RCD test

Functional test of every circuit

Energize circuit by circuit. Switch every light from every switch position. Plug a lamp or tester into every outlet. Run each appliance circuit (aircon, water heater, pump) with its equipment, and measure the current with a clamp meter to compare with the nameplate and the breaker. Open each breaker and confirm it kills exactly the circuit its label says. That last check catches mislabelled circuits, which are dangerous for the next person to work on them.

Labelling

Turnover documents

DocumentContents
As-built drawingsThe plans marked with every change made on site: moved outlets, rerouted runs, changed circuits.
Test resultsEach test, each circuit, the reading, the instrument used, the date and who tested.
Schedule of loads (updated)As installed, matching the panel directory.
Equipment informationManuals and warranty cards for devices supplied, where the job includes them.

Notify the supervisor when the tests are complete and give the results. Report any item you could not complete or that failed; don't leave it for someone else to discover. The supervisor or the person in charge decides on energizing and acceptance.

Cleaning up

On the job

Try it on the bench

  1. Open each breaker on the house bench in turn and check, with the multimeter, that exactly the outlets and lamps on its circuit go dead. Write a panel directory from what you find.
  2. With every breaker on, measure each outlet line to line and each line to ground, and record the readings like a test sheet.
  3. Run the ⏱ Test run and the 🛡 Safety check as your final inspection before "turnover".

Parts on the bench

In the course

Electrical Installation and Maintenance (NC II-aligned), module “9 · Testing, turnover and the final assessment”.

More on electrical installation